| Parameter | Waarde |
|---|---|
| Repeated hard short circuits can reduce the melting integral of the integrated backup fuse. | |
| EMC | A |
| Samensmelten | electronic |
| Opmerking | Connection for signal line tested in accordance with EN 61000-4-4 with 1 kV; if necessary, customer must provide appropriate protective measures |
| Type | DIN rail module, one-piece |
| Diepte | 55.6 mm (incl. DIN rail 7.5 mm) |
| Breedte | 6.2 mm |
| Hoogte | ≤ 3000 m up to 52 °C (amsl) |
| Vochtigheid | B |
| Materiaal | PBT |
| Omheining | A |
| Trilling | B |
| Efficiëntie | > 98.5 % |
| Temperatuur | A |
| Producttype | Device circuit breakers |
| Spanningsval | 0.28 V (at 0.5 A) |
| Vochtigheidstest | 96 h, 95 % RH, 40 °C |
| Montagetype | DIN rail: 35 mm |
| Nominale spanning | 24 V DC |
| Uitschakeltijd | ≤ 600 ms |
| Identificatie | UL/C-UL Listed UL 508 |
| Productfamilie | PTCB |
| Kanaal-LED uit | off (Channel switched off) |
| Kanaal-LED rood | lit (Channel switched off, over- or undervoltage active) |
| Verbindingsnaam | Remote indication circuit |
| Aantal kanalen | 1 |
| Triggermethode | E (electronic) |
| Vervuilingsgraad | 2 |
| Beschermingsklasse | III |
| Geschatte huidige IN | 15 A DC (Total current input) |
| Striplengte | 8 mm |
| Kanaal-LED groen | lit (Channel switched on) |
| Verbindingsmethode | Push-in connection |
| Dwarsdoorsnede AWG | (converted acc. to IEC) |
| Fail-safe element | 4 A DC |
| Bedrijfsstroom | 100 mA DC |
| Bedrijfsspanning | 10 V DC ... 30 V DC |
| Vermogensdissipatie | typ. 0.1 W (No-load operation) |
| Schok (operatie) | 30g (IEC 60068-2-27, Test Ea) |
| Kanaal-LED geel | flashing (Programming mode active) |
| Schakelfunctie | N/O contact |
| Diëlektrische sterkte | max. 35 V DC (Load circuit) |
| Maattekening | |
| Terugkoppelingweerstand | max. 35 V DC |
| Aantal posities | 1 |
| Nominale overspanningsspanning | 0.5 kV |
| Beschermingsgraad | IP20 |
| Maximale capacitieve belasting | 5.7 mF (Depending on the current setting and the short-circuit current available) |
| Vereiste reservezekering | Only required if Imaxof the power supply > the short-circuit switching capacity. Integrated failsafe element. |
| Temperatuurreductie | 15 A (Total current at 60°C) |
| Tolerantie meten I | ± 7 % |
| Trilling (werking) | 10 Hz ... 59.6 Hz (Amplitude ±0.35 mm; in accordance with IEC 60068-2-6, Test Fc) |
| Overspanningsbeveiliging | ≥ 30.5 V DC (active) |
| Onderspanningsbeveiliging | ≤ 9.2 V DC (active) |
| Normen/specificaties | EN 61000-6-2 |
| Actieve stroombeperking | typ. 1,1 x IN |
| Stroomsterkte in gesloten circuit I0 | typ. 5 mA |
| MTBF (IEC 61709, SN 29500) | 28514399 h (at 25 °C with 21 % load) |
| Module-initialisatietijd | 40 ms |
| Geleiderdoorsnede AWG | 24 ... 12 |
| Nominale stroomsterkte (vóór aanpassing) | 0.5 A |
| Geleiderdoorsnede stijf | 0.2 mm² ... 4 mm² |
| Omgevingstemperatuur (bedrijfstemperatuur) | -30 °C ... 60 °C |
| Flexibele doorsnede van de geleider | 0.2 mm² ... 2.5 mm² |
| Kortsluitschakelcapaciteit | 300 A |
| Brandbaarheidsclassificatie volgens UL 94 | V-0 |
| Omgevingstemperatuur (opslag/transport) | -40 °C ... 70 °C |
| Wachttijd na het uitschakelen van een kanaal | 5 s (at overload / short circuit) |
| Geleiderdoorsnede, flexibel, met adereindhuls, met plastic huls | 0.2 mm² ... 2.5 mm² |
| Flexibele geleiderdoorsnede, met ferrule zonder plastic huls. | 0.2 mm² ... 2.5 mm² |
Technische specificaties en prestatiegegevens